MTU C23R Instruções de Operação Página 103

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
Vista de página 102
7.8 Fuel System
7.8.1 Fuel system – Venting
Preconditions
Engine is stopped and starting disabled.
Special tools, Material, Spare parts
Designation / Use Part No. Qty.
Diesel fuel
WARNING
Fuels are combustible.
Risk of fire and explosion!
Avoid open flames, electrical sparks and ignition sources.
Do not smoke.
Venting LP fuel system
1. Open vent plug (1).
2. Unlock fuel priming pump (2), screw out
handle by turning it counterclockwise.
3. Operate the pump with the handle (2) until
bubble-free fuel emerges from the vent
plug (1).
4. Close vent plug (1).
5. Screw in handle by turning it clockwise.
6. Verify that fuel priming pump (2) is locked:
Handle must be tightened.
M015695/03E 2013-03 | Task Description | 103
TIM-ID: 0000004709 - 006
Vista de página 102
1 2 ... 98 99 100 101 102 103 104 105 106 107 108 ... 162 163

Comentários a estes Manuais

Sem comentários